MU nv / G-LEHRS





Enlarge Image

Enlarge Image

hover to enlarge

G5

TECHNICAL DATA BURNER G5

 

 

Fuel

Natural gas

 

Propane / Butane

Burner Capacity

25 - 100 kWatt

Mode of control

On / Off

Safety device

Safety & Control Box

Flame monitoring

Ionisation

Nominal motor capacity :

165 Watt

Nominal voltage

220 V - 50 / 60 Hz

Gas supply :

1/2 "

 

Natural gas : 25 - 70 mB

 

Propane / Butane : 35 - 50 mB

Gas valve :

220 V - 50 / 60 Hz   - 20 Watt

 

Max pressure : 500 mB

Operation heat values :

Natural Gas Low : Hu = 8.83 kWh / Nm³

 

Natural Gas High : Hu= 10.35 kWh / Nm³

 

Butane : Hu = 34.29 kWh / Nm³

 

Propane : Hu = 25.9 kWh / Nm³

Dimensions :

Width : 325 mm

 

Height : 625 mm

 

Depth : 250 mm

Weight net :

18 Kg

Weight gross :

19 Kg

 

 

TECHNICAL DATA SAFETY & CONTROL BOX

Nominal Voltage :

110 / 220 V - 50 / 60 Hz

Ignition time :

Variable 1 - 30 sec

Shut - off time :

Variable 1 - 30 sec

Run signal :

Contact closed - or - In 24/110/220V

Generated alarms :

Contact closed - or - Out 24/110/220V

Indications :

Burner heating : green

 

Burner in alarm : red

Dimensions :

H 400 x W 300 x D 220 mm – weight 9 Kg



Special demands:
Gas pressure: A small gas pressure regulator can be supplied with every burner.
Proportional: A special proportional version can be supplied.